Analog Output Setup

Analog Output Setup
The 9130 controller has the option of two (2) analog outputs. The outputs are ranged for a 4 – 20 milliamp signal or a 0 – 20 milliamp signal. Each output comes with a factory default configuration dependent on the application. Each output can be modified prior to shipment to your facility or in the field by a supervisor.

 

Analog Output Terminals

Analog output 1 – terminals 24 and 25

Analog output 2 – terminals 25 and 26

 

Assignment

The analog output assignment can be modified depending on your system requirements. To change the Assignment first select which analog output you want to change by selecting it in the pull-down menu at the top of the screen.  The following is a list of the options:

PV 1 retrans        Loop 3 dec

Loop 1 inc        Loop 3 combo

Loop 1 dec        Input 1 retrans

Loop 1 combo        Input 2 retrans

PV 2 retrans        Input 3 retrans

Loop 2 inc        SP1 retrans

Loop 2 dec        Programmer ID

Loop 2 combo        Disabled    

Loop 3 inc

 

Offset

This is the starting point, the Process Variable value at which you get 4 milliamps.  Clicking on this value will display an input box from which the user can select a new value.  The range is –32768 to 32767.

 

Range

This is a Process Variable value between 4 and 20 milliamps.  Clicking on this value will display an input box from which the user can select a new value.  The range is –32768 to 32767.

Note - The range, although not displayed with a decimal point, contains a decimal point that is dependent on the process variable selected. For example, if the offset is 20 mV for 4 mA, and you want 100 mV to be 20 mA, then your range should be 80. If the process variable is temperature, then the range will be 80, since temperature PVs do not have a decimal. If the PV is % Carbon, then the range will need to include the two decimal points for % Carbon. So, a range of 80 will be entered as 8000. See below for more examples.

 

Current Selection 

Provides the option of 4-20 mA or 0-20 mA control.  Clicking on this value will display an input box with a drop-down list from which the user can select either of the two values listed above.

 

Offset and Range when assigned to a control loop

Inc : 0 = 4mA, 100 = 20mA

Dec : 0 = 4mA, -100 = 20mA

 

Example: if 4 – 20 mA = 800 mV  - 1200 mV

    Offset  = 800 (starting point)

    Range = 400

 

The Return button will return the user to the menu screen.